Conventional or Constant Volume (CV)
The systems volumetric exhaust flow (Q) remains constant. Closing or opening sashes causes proportional increases or decreases in the face velocity (V) at the access opening area (A). Q=VA .
In automated systems, sash position sensors or switches can be used to control the ventilation system flow and compensate for this effect. Q follows A.
Bypass
Similar to a CV hood but bypass openings or dampers are added to open/close in opposition to the change in area of the sash opening.
This is not an even offset but it helps attenuate the face velocity changes and limits extreme velocities as the sash approaches completely closed positioning.
Note: Local controllers such as timers and on/off switches have been used for energy savings on older systems, these should all be disabled and replaced.